力士樂伺服驅動器維修:對工業設備進行任何故障排除之前,維護人員或負責故障排除和維修的人員應采取所有必要步驟,以確保其自身安全以及機械領域人員的安全。排除故障中涉及的每個人都有適當的鎖定,標記和確認機器無能耗的責任。完成所有關機程序后,只需過去,嘗試像操作員通常那樣啟動機器
力士樂伺服驅動器維修:故障解析:
D905故障含義:Wrong Position Range位置范圍錯誤
Description:故障說明:
Before starting an automatic control loop setting, both travel range limits,
i.e., upper and lower, must be defined.在開始自動控制回路設置之前,兩個行程范圍限制,i、 e.必須定義上限和下限。
When starting command P-0-0162, D9 automatic control loop setting the number values are automatically checked for validity. It is checked if
the traversing path is large enough and if sensible values have been
entered.當啟動命令P-0-0162、D9自動控制回路設置時,會自動檢查數值的有效性。檢查是否遍歷路徑足夠大,并且如果合理的值進入。
Possible fault causes:可能的故障原因:
• P-0-0167, upper traversing range smaller than P-0-0166, lower
traversing rangeP-0-0167,上部橫向范圍小于P-0-0166,下部橫向測量范圍
• Maximum traversing path (= upper - lower limits) is less than 6 motor
rotations and thus too small to start the automatic control loop setting.最大橫移路徑(=上限-下限)小于6個電機旋轉,因此太小,無法啟動自動控制回路設置。
Remedy:解決措施:
• clear command error by ending the command
通過結束命令來清除命令錯誤
• a) input new limits whereby:upper > lower limitsb) redefine limits to define a larger traversing rangea) 輸入新的極限:上限>下限b)重新定義極限以定義更大的穿越范圍
• restart command with sensible traversing range
具有合理遍歷范圍的重啟命令
力士樂伺服驅動器維修點:上海市嘉定區博園路858號,上海仰光電子科技有限公司專業從事各品牌伺服驅動器維修,伺服電機維修,觸摸屏維修,變頻器維修,伺服器維修,伺服控制器維修,數控系統維修改造,機器人維修保養以及各種板卡,芯片級維修維護,免費檢測,快速維修,部分立等可取!
轉載請注明出處:上海仰光電子科技專業伺服驅動器維修,伺服電機維修
本文鏈接:http://kukud.com.cn/fuwu/Services_Show12188.htm
伺服驅動器維修 伺服電機維修 觸摸屏維修 變頻器維修
電話:021-50157782
手機:13817011982 微信同號
郵箱:shygdzi@163.com
聯系人:張工
網址:http://kukud.com.cn
【 我們確保修好測試好給客戶。。!】
下一篇:常州INVY英威騰CHE100-011G-2變頻器OC報警故障維修